← All Advisories
Reported from OT-Advisories.com as of

Belden Hirschmann HiLCOS Classic Platform Stores User Passwords in Recoverable Format, Exposing Credentials to Adjacent Unauthenticated Attackers

Last refreshed2026-11-20

Status: UPDATED  |  Advisory ID: CVE-2016-15058

Key Details

CVECVE-2016-15058
CVSS Score / Version
8.1 (High) / CVSS v3.1
Updated2026-07-21
CVSS Vector
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
CVSS Prose
attack vector is adjacent; attack complexity is low; privileges required is none; user interaction is none; scope is unchanged; confidentiality impact is high; integrity impact is high; availability impact is none.
Affected products
Belden Hirschmann HiLCOS Classic Platform
Classified as
CWE-257 (Storing Passwords in a Recoverable Format)
Exploitation prediction (EPSS)
0.21% probability of exploitation in the next 30 days (12% percentile) -- FIRST.org's EPSS model.

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
BeldenHirschmann HiLCOS Classic Platform
SubsystemsGeneral OT
SectorsMultiple

What to Know

Hirschmann HiLCOS Classic Platform switches Classic L2E, L2P, L3E, L3P versions prior to 09.0.06 and Classic L2B prior to 05.3.07 contain a credential exposure vulnerability where user passwords are synchronized with SNMPv1/v2 community strings and transmitted in plaintext when the feature is enabled. Attackers with local network access can sniff SNMP traffic or extract configuration data to recover plaintext credentials and gain unauthorized administrative access to the switches. (NVD)

What to Do

For devices with versions 09.0.00 and higher: (1) disable the SNMP password synchronization feature, (2) set the SNMPv1/v2 communities to default values, (3) disable SNMPv1/v2 globally, (4) change the read and read/write passwords, (5) save the configuration. For devices with versions lower than 09.0.00: (1) change the read and read/write passwords, (2) set the SNMPv1/v2 communities to default values, (3) disable SNMPv1/v2 globally, (4) save the configuration -- repeating step (2) every time the password is changed.
Source: Belden

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2016-15058
CVEhttps://www.cve.org/CVERecord?id=CVE-2016-15058
Vendor advisoryhttps://assets.belden.com/m/1d8273c6205dc400/original/Security-Bulletin-Password-Sync-SNMP-v1-v2-BSECV-2016-12.pdf
Report compilation © 2026 OT-Advisories.com  ·  CC BY 4.0  ·  Source materials remain the property of their respective publishers as cited.