Pepperl+Fuchs ICE-Series IO-Link Masters Allow Low-Privileged Users to Upload Arbitrary IODD Files via a Missing Authorization Check, Enabling Device Manipulation or Crashes
Last refreshed2026-11-19
Status: UPDATED
| Advisory ID: CVE-2026-27552
Key Details
CVE
CVE-2026-27552
CVSS Score / Version
8.1 (High) / CVSS v3.1
Updated
2026-09-16
CVSS Vector
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:H
CVSS Prose
attack vector is network; attack complexity is low; privileges required is low; user interaction is none; scope is unchanged; confidentiality impact is none; integrity impact is high; availability impact is high.
Affected products
see table below
Classified as
CWE-863 (Incorrect Authorization)
Exploitation prediction (EPSS)
0.60% probability of exploitation in the next 30 days (50% percentile) -- FIRST.org's EPSS model.
Affected Products, Subsystems & Sectors
Vendor
Product
Affected Versions
Patch Status
Pepperl+Fuchs
ICE2-8IOL-K45P-RJ45
Pepperl+Fuchs
ICE2-8IOL1-G65L-V1D
Pepperl+Fuchs
ICE2-8IOL-G65L-V1D
Pepperl+Fuchs
ICE2-8IOL-K45S-RJ45
Pepperl+Fuchs
ICE3-8IOL1-G65L-V1D
Pepperl+Fuchs
ICE3-8IOL-G65L-V1D
Pepperl+Fuchs
ICE3-8IOL-G65L-V1D-Y
Pepperl+Fuchs
ICE3-8IOL-K45P-RJ45
Pepperl+Fuchs
ICE3-8IOL-K45S-RJ45
Phoenix Contact
IOL MA8 PN DI8
Phoenix Contact
IOL MA8 EIP DI8
Carlo Gavazzi Automation
YL212CEI8M1IO
Carlo Gavazzi Automation
YN115CEI8RPIO
Carlo Gavazzi Automation
YL212CPN8M1IO
Carlo Gavazzi Automation
YN115CPN8RPIO
Subsystems
Automation / MES, Controllers & Field I/O
Sectors
Multiple
What to Know
A low-privileged remote attacker can exploit improper authorization in the /index.php/attached_devices_tab/do_upload endpoint to upload IODD files to the device, potentially altering device behavior or causing system crashes.
What to Do
CVE-2026-27552: Incorrect Authorization (CWE-863). Summary: A low-privileged remote attacker can exploit improper authorization in the /index.php/attached_devices_tab/do_upload endpoint to upload IODD files to the device, potentially altering device behavior or causing system crashes. Affected Product(s): Pepperl+Fuchs ICE2-*/ICE3-* IO-Link Masters, Firmware < 1.7.4. Mitigation: Minimize network exposure for affected products and ensure that they are not accessible via the Internet. Isolate affected products from the corporate network. If remote access is required, use secure methods such as virtual private networks (VPNs). Remediation: Install the firmware update 1.7.8. Source: Pepperl+Fuchs SE (via CERT@VDE) VDE-2026-014