Affected productsSiemens SIMATIC IoT2050 Advanced
Classified asCWE-306 (Missing Authentication for Critical Function)

Affected Products, Subsystems & Sectors

VendorProductAffected VersionsPatch Status
SiemensSIMATIC IoT2050 Advanced
SubsystemsGeneral OT
SectorsMultiple

What to Know

A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions < V4.3.4.1 running Industrial OS with Node-RED installed). Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server.

This could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges. (NVD)

What to Do

Monitor Siemens's web page for any future patch releases.

References

SourceReference
NVDhttps://nvd.nist.gov/vuln/detail/CVE-2026-58115
CVEhttps://www.cve.org/CVERecord?id=CVE-2026-58115